The 3ABD00038167-D: Normal-use (110 kW, 206 A) covers constant-torque loads like conveyors and pumps. Heavy-duty (90 kW, 169 A) handles variable-torque or higher starting-torque applications such as crushers or extruders. The light-overload rating matches the normal-use power but at 196 A, useful where thermal margin is tight. Frame size R7 and wall-mounting simplify panel layout — no floor footprint needed.
WEEE category 4 (Large Equipment). The drive carries IE2 efficiency classification. Full RoHS, REACH, and UL/IEC compliance documentation is available from ABB upon request.