The 3ABD00038169-D: Normal-use rating of 160 kW / 293 A covers constant-torque applications like conveyors or pumps. Heavy-duty use drops to 132 kW / 246 A for higher starting torque or cyclic loads. Light-overload use is 160 kW / 278 A. Match the duty class to your motor's actual demand — oversizing on normal-use current risks nuisance trips on a high-inertia start.
Wall-mounted, IP21, NEMA 1. Suitable for indoor, clean environments. No gland plate or conduit kit included — plan for cable entry per the installation manual. The R8 frame is sized for the 293 A output; verify wall load capacity before hanging.