Skip to main content
ABB 3ABD00039315-D — AC Drive (VFD) 480V

ABB 3ABD00039315-D ACS880-04 Drive Module, 250 kW, 505 A

MPN3ABD00039315-D
Active

ABB ACS880-04 industrial single drive module, 3ABD00039315-D, 250 kW / 505 A, 380-415 V 3-phase, IP20, R10 frame.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00039315-D — Power & Output
ParameterValue
Output power, normal duty250 kW
Output current, normal duty505 A
Output power, heavy duty200 kW
Output current, heavy duty361 A
Output power, light overload250 kW
Output current, light overload485 A
Efficiency class (IE)IE2

Input / Supply

3ABD00039315-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00039315-D — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

Drive module for high-power cabinet builds

The ABB 3ABD00039315-D is an LV AC industrial single drive module rated for 250 kW normal use at 505 A output, with a heavy-duty rating of 200 kW at 361 A. It accepts 380–415 V three-phase input at 47.5–63 Hz and is built in an R10 frame with IP20 protection.

The heavy-duty current (IhD) of 361 A at 200 kW is the rating for higher overload demands — if your motor load requires sustained torque above the normal curve, size to the heavy-duty line. The light-overload rating (485 A, 250 kW) sits between the two and covers applications with infrequent overloads. Efficiency class IE2 means the module meets the baseline industrial motor-drive efficiency standard. For newer installations targeting IE3 or IE4, this module still works but may not be the most energy-optimized choice for continuous full-load operation.

Integration into a cabinet

The R10 frame is a standard cabinet-mount module with IP20 finger-safe protection. Mounting is module-style — it slides into a panel with appropriate bus-bar and cooling provisions. The open-type NEMA enclosure means the module is not self-contained — it relies on the surrounding cabinet for environmental sealing. Ensure the panel has adequate airflow for the 250 kW dissipation; forced cooling is typical at this power level.

Frequently asked questions

What are the key ratings for this drive module?

Normal-use output is 250 kW at 505 A; heavy-duty output is 200 kW at 361 A; light-overload output is 250 kW at 485 A. Input is 380–415 V three-phase, 47.5–63 Hz. Frame size is R10 with IP20 protection.

MPN