Skip to main content
ABB 3ABD00039339-D — AC Drive (VFD) 480V

ABB 3ABD00039339-D LV AC Drive Module, 500 kW / 880 A

MPN3ABD00039339-D
Active

ABB LV AC industrial single drive module, 3ABD00039339-D, Frame R10, 500 kW / 880 A normal use, 400 kW / 725 A heavy-duty, 380-415 V 3-phase, IP20, Open Type.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00039339-D — Power & Output
ParameterValue
Output power, normal duty500 kW
Output current, normal duty880 A
Output power, heavy duty400 kW
Output current, heavy duty725 A
Output power, light overload500 kW
Output current, light overload865 A

Input / Supply

3ABD00039339-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00039339-D — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

Drive module, 500 kW normal-use rating

The ABB 3ABD00039339-D is an LV AC industrial single drive module in the ACS880 family, rated for 500 kW normal-use output at 880 A, with a heavy-duty ceiling of 400 kW at 725 A. Input is 380-415 V three-phase, 47.5-63 Hz. Frame size R10, IP20, Open Type enclosure.

Normal-use (Pn 500 kW, In 880 A) covers continuous constant-torque applications like pumps and fans. Heavy-duty (PhD 400 kW, IhD 725 A) handles the higher peak demands of conveyors or crushers. Light-overload (PlD 500 kW, IlD 865 A) sits close to normal but with a slightly higher current ceiling for short-duration overloads.

Frame R10, IP20, Open Type. Mounts in a standard cabinet with clearance for airflow. Three-phase input at 380-415 V, 47.5-63 Hz. No special enclosure beyond the IP20 rating — plan for panel ventilation if ambient exceeds 40 °C.

Frequently asked questions

What is the frame size of 3ABD00039339-D?

Frame size R10.

What are the key electrical ratings?

Normal-use output: 500 kW, 880 A. Heavy-duty: 400 kW, 725 A. Light-overload: 500 kW, 865 A. Input: 380-415 V three-phase, 47.5-63 Hz.