Specifications

Power & Output

3ABD00039366-D — Power & Output
ParameterValue
Output power, normal duty400 kW
Output current, normal duty725 A
Output power, heavy duty315 kW
Output current, heavy duty566 A
Output power, light overload400 kW
Output current, light overload715 A

Input / Supply

3ABD00039366-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00039366-D — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule

Product details

What this drive module delivers

Heavy-duty use is rated 315 kW / 566 A, and light-overload use 400 kW / 715 A — so you pick the duty class that matches your load profile, not just the headline number. Frame size R11 tells the cabinet planner the physical envelope and bus-bar layout. This is a three-phase module accepting 380-415 V input at 47.5-63 Hz, so it covers 50 Hz and 60 Hz grids without reconfiguration. IP20 protection means it mounts inside an enclosure — no washdown rating, no outdoor exposure. The open-type NEMA classification confirms it needs a clean, dry cabinet with proper clearance for airflow and arc flash containment.

Duty ratings — which one governs your load

The 725 A normal-use rating (400 kW) fits centrifugal pumps, fans, and general conveyors where overload is light and infrequent. Heavy-duty at 566 A (315 kW) is the figure for extruders, crushers, or hoists that demand sustained torque at low speed. Light-overload at 715 A (400 kW) sits between them — useful for applications with occasional peak demand but not continuous hard duty. A common mistake is sizing on the normal-use number alone. If your motor draws 600 A during a start cycle that lasts 60 seconds, the heavy-duty curve is the one that keeps the module out of thermal trip. The datasheet's overload profile (not shown here) would confirm the exact time-current boundary.

Cabinet integration notes

Frame R11 drives the mounting footprint and bus-bar centers. Verify the cabinet depth allows for the DC-link bus bars and the optional braking chopper if your application needs dynamic braking. The IP20 enclosure means no gland plate sealing — route cables through the cabinet's own entry points and maintain separation between power and control wiring per the installation manual.

Frequently asked questions

What is the frame size of this drive module?

Frame size R11. This determines the physical dimensions, bus-bar layout, and mounting hole pattern for cabinet integration.

What input voltage and frequency does this module accept?

Three-phase input at 380-415 V, 47.5-63 Hz. This covers both 50 Hz and 60 Hz grids without hardware changes.

What are the key output ratings I should use for sizing?

Normal use: 400 kW / 725 A. Heavy-duty use: 315 kW / 566 A. Light-overload use: 400 kW / 715 A. Select the duty class matching your load profile — the heavy-duty figure governs for demanding applications like crushers or hoists.

What compliance documentation is available for this part?