It's rated for 315 kW normal-use output at 585 A, with heavy-duty capability at 250 kW / 429 A and light-overload at 315 kW / 575 A. Input is 3-phase 380-415 V, 47.5-63 Hz. IP20 open-type enclosure — plan for cabinet mounting with adequate cooling.
Light-overload at 575 A (IlD) splits the difference for applications with moderate overload profiles. IE2 efficiency class means it meets the base EU efficiency level — not premium, but compliant for most installations where the motor itself drives the system efficiency.
IP20 open-type enclosure — no integral touch protection on the power terminals, so it's intended for a locked cabinet or electrical room. Frame R11 is a standard ABB drive module footprint; verify cabinet depth and busbar layout against the mechanical drawing. WEEE Category 4 (large equipment) applies for end-of-life disposal tracking. No UL listing stated in the spec record — confirm with the factory if UL 508C or CSA is required for your jurisdiction.