It delivers 315 kW output power at 585 A in normal use, with a heavy-duty rating of 250 kW at 429 A for tougher loads. Input is 380-415 V three-phase, 47.5-63 Hz, and the unit carries an IE2 efficiency level. Frame size is R11, enclosure is IP20 Open Type — it's meant for a panel, not standalone.
Sizing and duty
The normal-use rating (315 kW, 585 A) covers continuous motor operation at full load. Heavy-duty use (250 kW, 429 A) applies when the drive sees overload cycles — conveyors, crushers, pumps with high starting torque. Light-overload use (315 kW, 575 A) sits close to normal but with a slightly different current curve. Pick the duty class that matches your load profile; the heavy-duty number is the one that keeps the drive alive on a tough line.
Frame R11 is a cabinet-mount module, IP20 rated — no external weatherproofing. Open Type NEMA enclosure means it needs a clean, dry panel environment. Three-phase input at 380-415 V, frequency range 47.5-63 Hz covers 50/60 Hz grids. The 585 A normal-use current dictates busbar and cable sizing; plan for adequate copper cross-section and ventilation around the heat sink.