ABB 3ABD00039789-D — AC Drive (VFD) 480V

ABB 3ABD00039789-D ACS880-01 Drive, 200 kW, 363 A, IP55

MPN3ABD00039789-D
Active

ABB ACS880-01 wall-mounted single drive, 3ABD00039789-D, 200 kW / 363 A normal use, IP55, NEMA 12, frame R9.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00039789-D — Power & Output
ParameterValue
Output power, normal duty200 kW
Output current, normal duty363 A
Output power, heavy duty160 kW
Output current, heavy duty293 A
Output power, light overload200 kW
Output current, light overload345 A
Efficiency class (IE)IE2
3ABD00039789-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00039789-D — Mechanical & Cooling
ParameterValue
Frame sizeR9
NEMA enclosure typeType12
Degree of protection (IP)IP55
Mounting typeWall-mounted

Product details

The ABB 3ABD00039789-D is an ACS880-01 wall-mounted single drive rated for 200 kW normal-use output at 363 A, with a heavy-duty rating of 160 kW at 293 A. It's a three-phase unit accepting 380–415 V input at 47.5–63 Hz, enclosed to IP55 and NEMA Type 12 — meaning it's built for floor- or wall-mounting in dusty or washdown environments without a separate cabinet. Frame size R9 tells you the mechanical footprint and gland-plate layout; if you're replacing an existing R9 ACS880-01, the bolt pattern and cable entry line up.

Duty-cycle selection: normal vs heavy vs light overload

Three output ratings let you match the drive to the load profile without oversizing. Normal-use (Pn 200 kW, In 363 A) covers constant-torque fans and pumps. Heavy-duty (PhD 160 kW, IhD 293 A) is the number to use for conveyors or extruders that pull full current during acceleration or jam recovery — it's the thermal limit for 150 % overload for 60 s. Light-overload (PlD 200 kW, IlD 345 A) splits the difference for variable-torque loads that rarely exceed nameplate. If your motor plate says 200 kW but the application cycles hard, spec from the heavy-duty column.

Enclosure and mounting constraints

Rated IE2 efficiency — this is the standard efficiency level for the drive itself (not the motor). For a 200 kW unit running 6000 hours a year, the difference between IE2 and IE3 in drive losses is measurable but rarely the deciding factor; the motor's efficiency class and the driven load's duty cycle dominate the energy bill. IE2 is still compliant for most industrial installations where the local code doesn't mandate IE3 for drives.

Frequently asked questions

What is the frame size of this drive?

Frame size R9.

What input voltage and frequency does it accept?

Three-phase 380–415 V, 47.5–63 Hz.

What are the normal-use and heavy-duty output ratings?

Normal-use: 200 kW at 363 A. Heavy-duty: 160 kW at 293 A.

What is the enclosure protection rating?

IP55 and NEMA Type 12 — dust-tight and protected against water jets.