It is built on Frame R10, accepts 380-415 VAC three-phase at 48-63 Hz, and carries an IP20 open-type NEMA enclosure.
This module carries three distinct duty ratings. Normal use (Pn) delivers 355 kW / 650 A — the figure for continuous constant-torque applications like conveyors or pumps. Heavy-duty use (PhD) is 250 kW / 477 A, which is the rating for cyclic or high-starting-torque loads such as crushers or extruders. Light-overload use (PlD) is 355 kW / 634 A, essentially matching normal use but with a slightly lower current limit, suited for variable-torque loads like fans and centrifugal pumps where overload duration is short.
Construction and mounting
Mounting type is Module — it is a drive module intended for cabinet integration, not a standalone wall-mount unit. Frame R10 defines the mechanical footprint and bus-bar interface; verify panel cutout and bus-bar spacing against the hardware manual. IP20 protection means it is suitable for clean, dry indoor environments only. The open-type NEMA enclosure is consistent with a module designed for installation inside a larger enclosure.
Rated for 380-415 VAC three-phase input, 48-63 Hz. The WEEE category is 4 — Large Equipment with any external dimension more than 50 cm, which aligns with the physical size of an R10 frame drive module.