Skip to main content
ABB 3ABD00058035-D — AC Drive (VFD) 480V

ABB 3ABD00058035-D ACS880-01 Drive, 110 kW, 206 A, Frame R7

MPN3ABD00058035-D
Active

ABB ACS880-01 LV AC industrial wall-mounted single drive, 3ABD00058035-D, 380–415 V 3-phase, 47.5–63 Hz, Frame R7, IP20, NEMA Open Type.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00058035-D — Power & Output
ParameterValue
Output power, normal duty110 kW
Output current, normal duty206 A
Output power, heavy duty90 kW
Output current, heavy duty169 A
Output power, light overload110 kW
Output current, light overload196 A
3ABD00058035-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00058035-D — Mechanical & Cooling
ParameterValue
Frame sizeR7
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeWall-mounted

Product details

The ABB 3ABD00058035-D is an ACS880-01 wall-mounted single drive rated for 110 kW normal use at 206 A output on a 380–415 V three-phase supply. Frame R7, IP20 enclosure, NEMA Open Type — sized for a panel install where the cabinet provides the environmental seal. Frequency range covers 47.5 to 63 Hz, so it handles both 50 and 60 Hz line feeds without derating.

Three output current ratings let you match the drive to the load profile. Normal use (In) is 206 A — that is your baseline for constant-torque applications like conveyors or pumps running at nameplate. Heavy-duty use (IhD) drops to 169 A at 90 kW, which covers high-starting-torque loads like crushers or extruders where the drive must deliver peak current without tripping. Light-overload use (IlD) sits at 196 A, 110 kW, for variable-torque loads such as fans and centrifugal pumps where overload duration is short.

For a critical spare — one in the cabinet — this is the straightforward call: it is the current catalog number, not a legacy variant.

Frequently asked questions

What is the frame size of 3ABD00058035-D?

The frame size is R7. This determines the physical mounting footprint and the available options slots for the ACS880-01 series.

What compliance documentation is available for this drive?

The drive carries standard ABB compliance documentation including CE marking for the Low Voltage Directive and EMC Directive. Specific declarations (RoHS, REACH, UL) are available on request through the ABB documentation portal tied to the order code.

MPN