Skip to main content
ABB 3ABD00058827-D — AC Drive (VFD) 480V

ABB 3ABD00058827-D ACS880-01 Drive, 0.75 kW, 2.4 A, Frame R1

MPN3ABD00058827-D
Active

ABB ACS880-01 industrial drive, 3ABD00058827-D, 0.75 kW normal use, 2.4 A output, 380-415 V 3-phase, IP21, wall-mounted, frame R1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3ABD00058827-D — Power & Output
ParameterValue
Output power, normal duty0.75 kW
Output current, normal duty2.4 A
Output power, heavy duty0.55 kW
Output current, heavy duty1.8 A
Output power, light overload0.75 kW
Output current, light overload2.3 A
Efficiency class (IE)IE2
3ABD00058827-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00058827-D — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

Drive selection note for a 0.75 kW motor

The ABB 3ABD00058827-D is an ACS880-01 wall-mounted drive sized for a 0.75 kW 3-phase induction motor on 380-415 VAC supply. Normal-use output current is 2.4 A, which covers most standard IEC motors at that power. If the load profile includes short-term overloads, the heavy-duty rating of 0.55 kW at 1.8 A gives the headroom for conveyors or pumps that cycle hard. Light-overload use matches the normal-use power at 0.75 kW but draws 2.3 A — a slight derating from the 2.4 A continuous figure, likely for applications with sustained high torque at low speed.

IP21 enclosure with NEMA Type 1 rating means it's suited for indoor, clean environments — no washdown or dust. Wall-mounted frame R1 keeps the footprint compact; verify clearance for cabling and cooling airflow per the installation manual.

Efficiency and frequency range

Rated IE2 efficiency level meets the minimum for most industrial applications in regions without mandatory IE3 requirements. Frequency input range of 47.5 to 63 Hz covers both 50 Hz and 60 Hz mains without derating.

Frequently asked questions

What is the difference between normal use and heavy-duty ratings?

Normal use is 0.75 kW at 2.4 A; heavy-duty use is 0.55 kW at 1.8 A. The heavy-duty rating provides a higher overload margin for demanding cyclic loads.