Skip to main content
ABB 3ABD00058836-D — AC Drive (VFD) 480V

ABB 3ABD00058836-D ACS880-01 Drive, 15 kW, 32 A, Frame R3

MPN3ABD00058836-D
Active

ABB ACS880-01, 3ABD00058836-D, wall-mounted LV AC drive, 15 kW / 32 A normal duty, 380–415 V 3-phase, IP21, NEMA 1, Frame R3, IE2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3ABD00058836-D — Power & Output
ParameterValue
Output power, normal duty15 kW
Output current, normal duty32 A
Output power, heavy duty11 kW
Output current, heavy duty25 A
Output power, light overload15 kW
Output current, light overload30 A
Efficiency class (IE)IE2

Input / Supply

3ABD00058836-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz

Mechanical & Cooling

3ABD00058836-D — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

Frame, mounting, and enclosure

The 3ABD00058836-D: Frame size R3 defines the physical footprint — it's a wall-mounted unit, not intended for rack or cabinet integration. The IP21 degree of protection and NEMA Type 1 enclosure mean it's suitable for indoor, dry environments where tools or fingers might contact the enclosure but no water spray is present. Plan for wall space and clearance around the gland plate for incoming cables.

Three duty classes are listed: normal use at 15 kW / 32 A, light-overload at 15 kW / 30 A, and heavy-duty at 11 kW / 25 A. The normal-duty figure is the continuous rating for fan and pump profiles; heavy-duty covers constant-torque or cyclic loads like conveyors or crushers. Light-overload sits between them — useful when occasional overloads are expected but not sustained.

Frequently asked questions

What is the frame size of this drive?

Frame size R3, which determines the physical dimensions and mounting hole pattern for wall installation.

What are the normal-duty and heavy-duty ratings?

Normal-duty: 15 kW at 32 A. Heavy-duty: 11 kW at 25 A. Light-overload: 15 kW at 30 A.