The 3ABD00058846-D: Normal-use (Pn) 132 kW / 246 A covers constant-torque fan/pump duty. Heavy-duty (PhD) 110 kW / 206 A handles higher overload cycles — crushers, conveyors, extruders. Light-overload (PlD) 132 kW / 234 A sits between, for applications with moderate peak demands. Pick the duty column that matches your motor's torque profile, not the highest headline number.
Wall-mounted, IP21, NEMA Type 1 indoor use. Frequency range 47.5–63 Hz. Frame R8.