The 3ABD00059267-D: Input is 380–415 V three-phase, 47.5–63 Hz — standard European industrial mains. The module is frame size R10, open-type (IP20), so it goes inside a cabinet; the panel builder provides cooling and protection.
The normal-use 650 A / 355 kW rating is the headline number for sizing against a standard 3-phase induction motor. The heavy-duty 477 A / 250 kW figure is the one to use for applications with frequent starts, high inertia, or short deceleration profiles — it tells you the module can deliver that current continuously under overload conditions. Light-overload (634 A) sits between the two and is typically used for pumps and fans.