Skip to main content
ABB 3AUD0000003143 — AC Drive (VFD) 480V

3AUD0000003143 ACH580 HVAC Drive, 400 Hp, 477 A, 460 V

MPN3AUD0000003143
Active

ABB ACH580 HVAC packaged ultra-low harmonic drive, 3AUD0000003143, 400 Hp UL light-overload, 477 A, 440-480 V, 3-phase, NEMA Type 1, IP21, frame size R11, 50/60 Hz.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AUD0000003143 — Input / Supply
ParameterValue
Input voltage range440 ... 480 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000003143 — Power & Output
ParameterValue
Output current, light overload (UL rating)477 A
Output power, light overload (UL rating, Hp)400 Hp
3AUD0000003143 — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeType1
Degree of protection (IP)IP21

Product details

What this drive carries and where it goes

The ABB 3AUD0000003143 is an ACH580-series HVAC packaged ultra-low harmonic drive that ships with the circuit breaker integrated — no separate disconnect to panel in. Rated 400 Hp light-overload per UL at 460 V, pushing 477 A continuous. That 477 A figure governs the feeder cable and the upstream protection; the drive itself is sized for the fan and pump loads typical in commercial HVAC, not for high-breakaway-torque conveyors. Input voltage range 440-480 V, 3-phase, 50/60 Hz. Frame size R11, NEMA Type 1 enclosure, IP21 — suitable for indoor equipment rooms where dust and dripping water are controlled, not for washdown or outdoor pit duty.

The 477 A UL light-overload rating is the real selection number — it tells you the drive can deliver that current continuously without tripping on a fan or pump load profile. The built-in circuit breaker saves panel space and wiring labour, but verify the branch-circuit SCCR coordination with your upstream transformer; the breaker's interrupting rating is part of the drive package. Frame R11 means the mounting footprint and gland-plate layout match the ACH580 R11 dimensional drawing — confirm clearance for the incoming cables and the cooling airflow path.

Compliance documentation

The ACH580 series carries UL listing per the UL mark on the nameplate. For RoHS and REACH declarations, ABB provides compliance certificates through their document portal — the drive's order code 3AUD0000003143 is the key for the search. No IEC or CE marks are listed in the spec record, but the UL listing covers North American installations.

Frequently asked questions

Where can I buy 3AUD0000003143 and how do I get a price?

This drive is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 3AUD0000003143's listed frame size?

The frame size is R11, which determines the mounting footprint, gland-plate layout, and cable entry provisions for this ACH580 drive.

What is 3AUD0000003143's rated frequency?

The drive is rated for 50/60 Hz, covering both 50 Hz and 60 Hz supply systems without derating.

What compliance documentation does this brand provide for 3AUD0000003143?

ABB provides UL listing documentation for the ACH580 series. RoHS and REACH compliance certificates are available through ABB's document portal using the order code 3AUD0000003143.

MPN
3AUD0000003143