Skip to main content
ABB 3AUD0000003573 — AC Drive (VFD) 480V

ABB 3AUD0000003573 HVAC Drive, 100 Hp, 124 A, 460 V

MPN3AUD0000003573
Active

ABB ACH580 series HVAC enclosed ultra-low harmonic drive with circuit breaker, 3AUD0000003573, R8 frame, 100 Hp UL light-overload, 124 A output, 440-480 V, 3-phase, 50/60 Hz, IP21, NEMA Type 1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AUD0000003573 — Input / Supply
ParameterValue
Input voltage range440 ... 480 V
Number of phases3-phase
Frequency50/60 Hz
3AUD0000003573 — Power & Output
ParameterValue
Output current, light overload (UL rating)124 A
Output power, light overload (UL rating, Hp)100 Hp
3AUD0000003573 — Mechanical & Cooling
ParameterValue
Frame sizeR8
NEMA enclosure typeType1
Degree of protection (IP)IP21

Product details

The ABB 3AUD0000003573 is an ACH580-series HVAC enclosed ultra-low harmonic drive, factory-fitted with a circuit breaker. It delivers 100 Hp continuous output under UL light-overload duty, drawing 124 A at 460 V. The R8 frame houses a 3-phase input section rated for 440... 480 V, 50/60 Hz. The IP21 and NEMA Type 1 enclosure suits indoor installation in mechanical rooms or equipment closets — no washdown exposure, but adequate for dry HVAC plant environments. The integrated circuit breaker simplifies panel wiring by combining drive and branch-circuit protection in one footprint.

The 100 Hp / 124 A light-overload rating is the UL-listed continuous output for a typical HVAC load profile — fans, pumps, compressors running below 110 % rated current. The 440... 480 V input range covers 460 V nominal supplies common in North American industrial plants. The R8 frame size determines mounting hole pattern, gland-plate entry, and overall cabinet depth; verify the existing enclosure has the clearance before committing the BOM line.

Installation context

Mount the drive on a flat vertical surface inside the NEMA 1 enclosure; allow minimum clearance above and below for airflow per the ACH580 installation manual. The integrated circuit breaker serves as the disconnecting means — no separate branch breaker needed upstream if the SCCR rating matches the available fault current. Wire the 3-phase input through the gland plate; torque lugs to the values stamped on the bus bar.

Frequently asked questions

How do I get current pricing and availability for 3AUD0000003573?

Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the frame size and what does it mean for installation?

The frame size is R8. This determines the mounting footprint, gland-plate entry, and minimum cabinet depth — verify your enclosure has the required clearance before ordering.

What compliance documentation does ABB provide for this drive?

The drive carries UL listing (UL 508C) as standard for the North American market. RoHS and REACH declarations are available from ABB's documentation portal. No IEC or CE marking is noted on this specific variant.

MPN
3AUD0000003573