Input and environmental
The 3AXD50000031889: Input voltage range is 380–480 V AC, three-phase, at 47.5–63 Hz. Enclosure is IP20 (open type per NEMA), so it belongs in a clean, dry cabinet, not on the machine frame. Standby loss is 15 W; full-load power consumption is 62 W, with a power factor of 0.98.
The control unit includes 2 analog inputs, 1 analog output, 5 digital inputs, and 2 digital outputs — enough for basic speed reference, run/stop, and fault feedback. Modbus is the onboard protocol; there are no industrial Ethernet interfaces on this variant, so if the line uses PROFINET or EtherNet/IP, you will need a separate fieldbus adapter module.