Skip to main content
ABB 3AXD50000034608 — AC Drive (VFD) 480V

ABB 3AXD50000034608 ACQ580-01 Drive, 200 kW, 363 A, IP21

MPN3AXD50000034608
Active

ABB ACQ580-01, LV AC wall-mounted drive, 200 kW / 363 A normal use, 380-480 V, IP21, frame R9.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000034608 — Power & Output
ParameterValue
Output power, normal duty200 kW
Output current, normal duty363 A
Output power, heavy duty160 kW
Output current, heavy duty293 A
Output power, light overload200 kW
Output current, light overload345 A
Apparent power output251 kV·A
Efficiency class (IE)IE2
Standby power loss80 W
3AXD50000034608 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000034608 — Mechanical & Cooling
ParameterValue
Frame sizeR9
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000034608 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3AXD50000034608 is a wall-mounted LV AC drive for water and wastewater. It delivers 200 kW normal-use output at 363 A, with a heavy-duty rating of 160 kW / 293 A and light-overload rating of 200 kW / 345 A.

Power and mounting

Input is 380–480 V three-phase, 47.5–63 Hz. Frame R9, wall-mounted, IP21 with NEMA Type 1 enclosure — suitable for indoor installation where drips and falling dirt are the main concern. Maximum ambient 40 °C, altitude up to 4000 m before derating. Standby loss is 80 W, apparent power output 251 kV·A, power factor 0.98. Sound level 68 dB(A) — noticeable in a quiet pump room but typical for an R9 frame at this power. Includes a control unit; analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 3 outputs. Communication via CAN — no onboard Industrial Ethernet, so plan for an external fieldbus adapter if you need PROFINET or EtherNet/IP. Onboard battery is a CR2032 lithium coin cell, 220 mAh, 3 V — keeps the real-time clock and parameter backup alive during power-down. Replaceable, standard cell.

SCIP number 67c5daab-da3d-4123-804b-53a83b6d9528 Finland is on file — relevant for EU waste framework reporting under WEEE Category 4 (Large Equipment).

Frequently asked questions

What compliance documentation does ABB provide for this drive?

RoHS compliant per EU Directive 2011/65/EU and amendment 2015/863 (RoHS date 20240508). REACH registered (date 20250905) with a declaration that substances above 0.1 mass percentage are present. SCIP number 67c5daab-da3d-4123-804b-53a83b6d9528 Finland is on file for EU waste reporting.

What are the key ratings for this drive?

Normal-use output: 200 kW / 363 A. Heavy-duty: 160 kW / 293 A. Light-overload: 200 kW / 345 A. Input: 380–480 V three-phase, 47.5–63 Hz. IP21, NEMA Type 1, frame R9, wall-mounted.

What is the SCIP number for this drive?

SCIP number: 67c5daab-da3d-4123-804b-53a83b6d9528 Finland.

MPN
3AXD50000034608