Skip to main content
ABB 3AXD50000034626 — AC Drive (VFD) 480V

ABB 3AXD50000034626 ACQ580-01 Drive, 75 kW, 145 A, IP55

MPN3AXD50000034626
Active

ABB ACQ580-01 wall-mounted drive, 3AXD50000034626, 75 kW / 145 A normal use, 380-480 V, IP55, frame R6.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000034626 — Power & Output
ParameterValue
Output power, normal duty75 kW
Output current, normal duty145 A
Output power, heavy duty55 kW
Output current, heavy duty105 A
Output power, light overload75 kW
Output current, light overload138 A
Apparent power output100 kV·A
Efficiency class (IE)IE2
Standby power loss36 W
3AXD50000034626 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000034626 — Mechanical & Cooling
ParameterValue
Frame sizeR6
NEMA enclosure typeType12
Degree of protection (IP)IP55
Mounting typeWall-mounted
3AXD50000034626 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The 3AXD50000034626: The drive is rated IP55 with a NEMA Type 12 enclosure, making it suitable for washdown areas and dusty environments common in water treatment plants. Frame size R6 keeps the footprint manageable for wall mounting, and the maximum ambient temperature is 40 °C.

Input frequency range of 47.5-63 Hz covers weak grid conditions common on generator-backed sites. The power factor of 0.98 is the drive-side input displacement factor at rated load; no external harmonic filter is needed for most installations. Standby loss of 36 W matters for energy-conscious sites where the drive idles for extended periods. The 67 dB(A) sound level is typical for an R6 frame at full fan speed — locate it away from operator stations if noise is a concern.

The drive includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs — enough for a basic pump station with level transducer, flow meter, and start/stop commands. Communication is via CAN; no onboard Ethernet, so plan for a fieldbus adapter if the plant uses PROFINET or EtherNet/IP. A CR2032 lithium coin cell (220 mAh, 3 V) backs the real-time clock and parameter storage. Replace it during preventive maintenance to avoid losing configuration after a power loss.

Efficiency class IE2 is the standard rating. For projects requiring IE3 or IE4, verify that the specific pump/motor combination meets the local energy directive — the drive itself does not limit the system efficiency class.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 75 kW at 145 A; heavy-duty output is 55 kW at 105 A; light-overload output is 75 kW at 138 A. Input is 380-480 V three-phase.

What enclosure protection does this drive have?

IP55 with NEMA Type 12, suitable for washdown and dusty environments. Maximum ambient temperature is 40 °C.

What compliance documentation is available for this drive?

RoHS compliant per EU Directive 2011/65/EU (RoHS date 20240508). REACH declaration confirms substances >0.1 mass percentage (REACH date 20250905). SCIP number b9a3ab71-37fd-43f7-871e-9bf969163e13 Finland is registered under WEEE Category 4.

MPN