Duty and ratings
The 3AXD50000034631: Three duty points are specified: normal use (Pn) 200 kW at 363 A, heavy-duty (PhD) 160 kW at 293 A, and light-overload (PlD) 200 kW at 345 A. The heavy-duty figure governs continuous motor load in a pump or fan application where the drive runs near full rating; the light-overload figure covers intermittent peak demand. Apparent power output is rated 251 kV·A. Efficiency class is IE2. Standby loss runs 80 W, and the drive draws 4839 W at rated load. Power factor is 0.98.
IP55 with NEMA Type 12 enclosure — suitable for wall mounting in indoor wet or dusty environments like pump stations and treatment plants. Maximum ambient temperature is 40 °C, operating humidity 5–95% non-condensing, altitude up to 4000 m derated. Sound level is 68 dB(A).
I/O and interfaces
Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs. Communication is CAN-based; there are no industrial Ethernet interfaces. Frame size is R9.