It delivers 250 kW normal-use output (430 A) on a 380–480 V three-phase supply, with heavy-duty and light-overload ratings at 200 kW (363 A) and 200 kW (400 A) respectively. Frame size R9, IP55 / NEMA Type 12 enclosure, and a maximum 40 °C ambient.
Duty ratings that govern real pump loads
The drive has three output ratings: normal use (Pn) 250 kW / 430 A, heavy-duty (PhD) 200 kW / 363 A, and light-overload (PlD) 200 kW / 400 A.
IP55 / NEMA Type 12 means it handles hose-down and dust in treatment plants or outdoor shelters. Rated for 4000 m altitude without derating — relevant for pump stations at elevation. Ambient max 40 °C, humidity 5–95% non-condensing. Standby loss is 80 W; sound level 68 dB(A) — audible but not intrusive in a machinery room.
I/O and communication — what is on board
Standard complement: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. Communication is CAN-based — no onboard Industrial Ethernet (0 hardware interfaces for that). If you need Modbus TCP or PROFINET, plan for an option module. The control unit is included. A CR2032 lithium coin cell (220 mAh, 3 V) backs the real-time clock and parameter storage.