Skip to main content
ABB 3AXD50000035839 — AC Drive (VFD) 480V

ABB 3AXD50000035839 ACS880-01 Drive, 4 kW, 7.2 A, IP21

MPN3AXD50000035839
Active

ABB ACS880-01 series, LV AC industrial wall-mounted single drive, 4 kW, 7.2 A, 440 V, 3-phase, IP21, Type 1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000035839 — Power & Output
ParameterValue
Output power, normal duty4 kW
Output current, normal duty7.2 A
Output power, heavy duty2.2 kW
Output current, heavy duty4.9 A
Output power, light overload4 kW
Output current, light overload7.2 A
Output current, light overload (UL rating)7.2 A
Apparent power output5.5 kV·A
Efficiency class (IE)IE2
Standby power loss24 W
3AXD50000035839 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000035839 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000035839 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

Drive identity and ratings

The 3AXD50000035839: Frame size R1 keeps the footprint compact for a 4 kW drive, and the IP21 / NEMA Type 1 enclosure handles clean indoor environments fine — no washdowns, but okay for a dry panel or machine-mounted install.

Duty-cycle selection

Three output current ratings let you match the drive to the load profile. Light-overload and normal-duty both carry 7.2 A (4 kW); heavy-duty drops to 4.9 A (2.2 kW). If your motor nameplate says 5 A and the load is a fan or pump with low starting torque, you've got headroom. For a crusher or a press, you size off the heavy-duty number.

Environmental limits

Rated for a maximum 40 °C ambient and altitude up to 4000 m — above that you'd need to derate, but for most installations that's plenty of margin. The 50 dB(A) noise level is about what you'd expect from a drive this size; nothing that'll bother you in a machine hall. Standby loss of 24 W means the drive pulls a few watts even when the motor's stopped — factor that into panel cooling if you're running multiple drives in a sealed enclosure.

Frequently asked questions

What are the key output ratings for this drive?

Normal-duty output is 4 kW at 7.2 A; heavy-duty use is 2.2 kW at 4.9 A. Input is 380–480 V three-phase.

What enclosure protection does it have?

IP21 with NEMA Type 1 — suitable for indoor, dry locations.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863, and REACH registered with a declaration of substances above 0.1% mass.

MPN