The 3AXD50000035911: The normal-use output (Pn) of 1.5 kW at 3.9 A is the continuous rating for a standard-duty motor load. Heavy-duty use (PhD) drops to 1.1 kW at 3.0 A — that's the figure to watch if the application involves constant high torque or frequent overloads. Light-overload use (PlD) matches the normal-use numbers at 1.5 kW and 3.9 A, so there's no headroom penalty for occasional peak loads. Standby loss sits at 23 W, and total power consumption at rated load is 58 W. That's low enough to skip forced cooling in most wall-mounted enclosures, but the 40 °C maximum ambient still governs — derate if the cabinet runs hotter. The drive accepts 380-415 V three-phase at 47.5-63 Hz. IP21 and NEMA Type 1 enclosure suits clean indoor panels.
I/O and communication at a glance
You get 2 analog inputs and 2 analog outputs for process signals, plus 6 digital inputs and 2 digital outputs for basic control. Communication is CAN-based — no onboard Ethernet, so if the line needs Modbus TCP or PROFINET, plan for an external gateway or option module.