The 3AXD50000035913: Rated for 3 kW normal-use output at 7.5 A, with a heavy-duty rating of 2.2 kW at 5.8 A. Input is 380-415 V three-phase, 47.5-63 Hz. Enclosure is IP21 / NEMA Type 1, wall-mounted. Standby loss is 23 W; full-load power consumption is 109 W. Ambient temperature max is 40 °C.
The normal-use (light-overload) output is the same 3 kW / 7.5 A — this drive is sized for constant-torque loads like conveyors or pumps that don't need a heavy-overload cushion. The heavy-duty rating of 2.2 kW / 5.8 A gives you a 40% overload margin for 1 minute, enough for a centrifuge or a crusher start. No UL output ratings are listed for this variant, so if your panel requires UL listing on the nameplate, verify that the specific UL-marked version (typically a different order code) is used. The IEC ratings here are the ones that govern for CE-marked installations.
Built-in I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 2 digital outputs. Communication is CAN — no onboard Ethernet, so if you need PROFINET or EtherNet/IP, you'll add an option module.