ABB 3AXD50000035922 — AC Drive (VFD) 480V

ABB 3AXD50000035922 ACS880-01 Drive, 37 kW, 85 A, R5

MPN3AXD50000035922
Active

ABB ACS880-01 series, LV AC industrial wall-mounted single drive, 37 kW / 85 A normal use, 30 kW heavy-duty, R5 frame, IP21, includes control unit.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000035922 — Power & Output
ParameterValue
Output power, normal duty37 kW
Output current, normal duty85 A
Output power, heavy duty30 kW
Output current, heavy duty69 A
Output power, light overload37 kW
Output current, light overload83 A
Output current, light overload (UL rating)- A
Apparent power output59 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)- Hp
Standby power loss30 W
3AXD50000035922 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000035922 — Mechanical & Cooling
ParameterValue
Frame sizeR5
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000035922 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000035922 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)- Hp
Technical UL/Output Current, Heavy-Duty Use (UL)- A

Product details

The 3AXD50000035922: The drive includes a control unit as standard, with 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is via CAN. Standby loss is 30 W; power consumption at rated load is 1207 W.

Duty ratings and application fit

Normal-use output (Pn 37 kW, In 85 A) covers constant-torque applications like conveyors and pumps. Heavy-duty use (PhD 30 kW, IhD 69 A) handles higher overloads for extruders or crushers. Light-overload use (PlD 37 kW, IlD 83 A) matches variable-torque loads such as fans and centrifugal pumps. Apparent power output is 59 kVA. Efficiency level IE2. Maximum ambient temperature 40 °C; operating humidity 5–95% non-condensing.

Physical and mounting

Wall-mounted design, NEMA Type 1 enclosure (IP21). Frame size R5. The unit includes a lithium coin cell CR2032 (220 mAh, 3 V) for backup; two cells supplied, total 6 g. WEEE category 4 (large equipment over 50 cm).

Frequently asked questions

What are the key output ratings for this drive?

Normal use: 37 kW, 85 A. Heavy-duty use: 30 kW, 69 A. Light-overload use: 37 kW, 83 A.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH compliant with substances above 0.1% (date 20250320). UL ratings are not listed for this variant.

What I/O and communication does it include?

Includes control unit with 2 analog inputs, 2 analog outputs, 6 digital inputs, 2 digital outputs, and CAN communication.