Skip to main content
ABB 3AXD50000035923 — AC Drive (VFD) 480V

ABB 3AXD50000035923 ACS880-01 Control Unit, Frame R6, 45 kW

MPN3AXD50000035923
Active

ABB ACS880-01 control unit, Frame Size R6, 45 kW / 103 A, 380-415 V, IP21, wall-mounted.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000035923 — Power & Output
ParameterValue
Output power, normal duty45 kW
Output current, normal duty103 A
Output power, heavy duty37 kW
Output current, heavy duty85 A
Output power, light overload45 kW
Output current, light overload103 A
Output current, light overload (UL rating)- A
Apparent power output71 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)- Hp
Standby power loss42 W
3AXD50000035923 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000035923 — Mechanical & Cooling
ParameterValue
Frame sizeR6
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000035923 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000035923 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)- Hp
Technical UL/Output Current, Heavy-Duty Use (UL)- A

Product details

This ABB 3AXD50000035923 is the control unit for a drive in frame size R6. It includes the control electronics and firmware for the drive module, not the power stage itself. Rated for 45 kW normal-duty use at 103 A output, with heavy-duty ratings of 37 kW / 85 A. Input voltage range is 380–415 V three-phase, 47.5–63 Hz. Enclosure is IP21, Type 1 NEMA, wall-mounted. Standby losses are 42 W at 40 °C ambient max.

Integration and connectivity notes

Control unit provides 2 analog inputs, 2 analog outputs, 6 digital inputs, 2 digital outputs. Communication via CAN bus; no onboard Industrial Ethernet interface. Operates in 5–95% relative humidity. Mounting is wall-mounted only; ensure adequate airflow for the 42 W standby thermal load. Contains two CR2032 lithium coin cells (3 V, 220 mAh each) for backup. Verify battery date on nameplate during installation.

Frequently asked questions

What frame size is this control unit for?

This control unit is designed for ACS880-01 drives with frame size R6.

What does this part include?

The part includes the control unit only — no power module or cabling.

MPN
3AXD50000035923