Duty Ratings and Overload Capability
The 3AXD50000035924: Normal-use output is 55 kW / 123 A. Heavy-duty use steps down to 45 kW / 103 A, while light-overload use matches the normal-use current at 123 A. The apparent power output is 85 kV·A. Standby loss is 42 W; full-load power consumption is 1609 W.
Wall-mounted, rated for ambient temperatures up to 40 °C, operating humidity 5–95% RH. Frequency range 47.5–63 Hz. IP21 degree of protection and NEMA Type 1 enclosure suit indoor installations with limited dust and drip exposure.
Two analog inputs and two analog outputs. Six digital inputs and two digital outputs. Communication via CAN protocol; no industrial Ethernet interface on this variant. A lithium coin cell (CR2032, 220 mAh) backs up the real-time clock.