Skip to main content
ABB 3AXD50000038960 — AC Drive (VFD) 480V

ABB 3AXD50000038960 ACS580-01 VFD, 11 kW, 25 A, IP21

MPN3AXD50000038960
Active

ABB ACS580-01 general purpose wall-mounted drive, 3AXD50000038960, 11 kW / 25 A, 380-480 V, IP21, Frame R2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000038960 — Power & Output
ParameterValue
Output power, normal duty11 kW
Output current, normal duty25 A
Output power, heavy duty7.5 kW
Output current, heavy duty17.0 A
Output power, light overload11.0 kW
Output current, light overload23.8 A
Apparent power output17 kV·A
Efficiency class (IE)IE2
Standby power loss15 W
3AXD50000038960 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000038960 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000038960 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

This 3AXD50000038960 is a wall-mounted drive rated 11 kW output power and 25 A output current in normal-duty use (light-overload: 11.0 kW / 23.8 A). Heavy-duty use drops to 7.5 kW / 17.0 A. Input voltage covers 380 to 480 V three-phase, 47.5 to 63 Hz. Enclosure is IP21 with a NEMA Type 1 rating.

The normal-duty 25 A output (11 kW) is what you'd size for a variable-torque load — fans, centrifugal pumps. The heavy-duty 17 A (7.5 kW) is the real limit for constant-torque or high-starting-torque applications. If your motor plate says 11 kW and it's a compressor, you need the heavy-duty column, and this drive only delivers 7.5 kW there. That mismatch trips up a lot of first-time specifiers. Frame size R2, wall-mounted. Standby loss is 15 W, and at full load it draws 383 W from the line. Sound level is 64 dB(A) — noticeable in a quiet control room, fine on a plant floor.

Built-in I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 digital outputs. That's enough for basic speed reference, run/stop, and a fault relay without an add-on card. Communication is CAN-based — no onboard Ethernet (0 industrial Ethernet interfaces), so if you need Modbus TCP or PROFINET, plan for an optional fieldbus adapter module.

Compliance and environment

Includes control unit in the package. The internal CR2032 lithium coin cell (220 mAh, 3 V) keeps the real-time clock and parameter backup alive during power loss.

Frequently asked questions

What are the key ratings for this drive?

Normal-duty output is 11 kW / 25 A; heavy-duty output is 7.5 kW / 17 A. Input voltage is 380-480 V three-phase, 47.5-63 Hz. Enclosure is IP21 / NEMA Type 1.

What compliance documentation is available for this part?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. REACH registered (contains substances > 0.1% mass). SCIP number 4a4ed2db-43e7-4612-8e9c-3921e4acd08b Finland is on file.

MPN
3AXD50000038960