Overload ratings and duty selection
The 3AXD50000038961: Normal-use (Pn) is 15 kW at 32 A. Heavy-duty (PhD) is 11.0 kW at 24.6 A. Light-overload (PlD) is 15.0 kW at 30.4 A. The heavy-duty figure governs continuous operation at higher ambient or lower airflow — size the motor branch circuit to the IhD current if the load profile includes sustained overloads.
IP21 enclosure, NEMA Type 1, wall-mounted. Maximum ambient 40 °C, altitude 1000 m without derating. Operating humidity 5-95% RH. Frame size R3. Standby loss is 16 W; total power consumption at rated load is 492 W. Sound level 76 dB(A).
Onboard I/O: 6 digital inputs, 3 digital outputs, 2 analog inputs, 2 analog outputs. Communication via CAN; no onboard Industrial Ethernet. The control unit is included.