3AXD50000038969 — Power & Output
ParameterValue
Output power, normal duty4 kW
Output current, normal duty9.4 A
Output power, heavy duty3.0 kW
Output current, heavy duty7.2 A
Output power, light overload4.0 kW
Output current, light overload8.9 A
Apparent power output6.5 kV·A
Efficiency class (IE)IE2
Standby power loss14 W
3AXD50000038969 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000038969 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType12
Degree of protection (IP)IP55
Mounting typeWall-mounted
3AXD50000038969 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C

Product details

Duty ratings and real-world fit

The heavy-duty (PhD) rating of 3.0 kW at 7.2 A applies for constant-torque loads such as conveyors or positive-displacement pumps where the drive must hold torque at low speed. The apparent power output of 6.5 kV·A gives a quick cross-check against transformer sizing upstream.

The drive includes 2 analog inputs, 2 analog outputs, and 6 digital inputs with 3 digital outputs — enough for basic speed reference, feedback, and run/stop control without an expansion module. Communication is via CAN; there is no onboard Industrial Ethernet interface, so if you need PROFINET or EtherNet/IP, plan for an optional fieldbus adapter. The control unit is included, so no separate ordering of the keypad or logic board.

Environmental limits and mounting

The wall-mounted Frame R1 enclosure is IP55 / NEMA Type 12, meaning it is dust-protected and can handle hose-down cleaning — common in food-and-beverage or light industrial lines. Standby loss is 14 W, and sound pressure is 59 dB(A) at full load. The power consumption figure of 136 W is the drive's own internal losses, not the motor draw.

Frequently asked questions

What compliance documentation does this drive carry?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1% mass percentage (date 20250905). SCIP number 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland is on file. WEEE category 5 applies.

What is the altitude rating for this drive?

Rated for installation at altitudes up to 1000 m without derating.

What are the key output ratings for normal and heavy duty?

Normal use: 4 kW at 9.4 A. Heavy-duty use: 3.0 kW at 7.2 A. Light-overload use: 4.0 kW at 8.9 A.

What enclosure protection does this drive have?