Skip to main content
ABB 3AXD50000038979 — AC Drive (VFD) 480V

ABB 3AXD50000038979 ACS580-01 Drive, 18.5 kW, 38 A, IP55

MPN3AXD50000038979
Active

ABB ACS580-01 general purpose drive, order code 3AXD50000038979, 18.5 kW / 38 A normal use, 380-480 V 3-phase, IP55, frame R3, wall-mounted.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000038979 — Power & Output
ParameterValue
Output power, normal duty18.5 kW
Output current, normal duty38 A
Output power, heavy duty15.0 kW
Output current, heavy duty31.6 A
Output power, light overload18.5 kW
Output current, light overload36.1 A
Apparent power output26 kV·A
Efficiency class (IE)IE2
Standby power loss16 W
3AXD50000038979 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000038979 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeType12
Degree of protection (IP)IP55
Mounting typeWall-mounted
3AXD50000038979 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C

Product details

The ABB 3AXD50000038979 is a general-purpose wall-mounted drive rated for 18.5 kW normal use at 38 A output on a 380-480 V three-phase supply. It includes the control unit.

The normal-use output current of 38 A (In) is the number to match against your motor nameplate. If your application cycles hard, the heavy-duty rating of 31.6 A (IhD) gives you headroom. Light-overload use is rated at 36.1 A (IlD) — same 18.5 kW power as normal use, but with a slightly lower current ceiling. The drive is IP55 and NEMA Type12, so it's fine for dusty or washdown environments indoors. Ambient temperature max is 50 °C, and it's rated for altitudes up to 1000 m without derating.

Installation notes

Wall-mounted in frame R3. The drive has 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs. Communication is CAN-based — no onboard Ethernet, so if you need fieldbus, plan for an option module. Standby loss is 16 W; power consumption under load is 523 W. The sound level is 76 dB(A) — noticeable in a quiet control room. The battery is a CR2032 lithium coin cell for the real-time clock.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance per EU Directive 2011/65/EU (date 20240508) and REACH declaration (date 20250905) are on file. SCIP number 7ab39eb4-9330-424a-b7ff-fcf491eb4b83 applies.

What is the normal-use output rating?

18.5 kW at 38 A, on a 380-480 V three-phase supply. Heavy-duty rating is 15.0 kW at 31.6 A.

MPN
3AXD50000038979