Skip to main content
ABB 3AXD50000038997 — AC Drive (VFD) 480V

ABB 3AXD50000038997 ACH580-01 HVAC Drive, 22 kW, 45 A

MPN3AXD50000038997
Active

ABB ACH580-01 wall-mounted LV AC drive, 3AXD50000038997, 22 kW / 45 A normal use, 380-480 V 3-phase, IP21, BACnet, frame R3.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000038997 — Power & Output
ParameterValue
Output power, normal duty22 kW
Output current, normal duty45 A
Output power, heavy duty18.5 kW
Output current, heavy duty37.7 A
Output power, light overload22.0 kW
Output current, light overload42.8 A
Output current, light overload (UL rating)44.0 A
Apparent power output31 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)30 Hp
Standby power loss16 W
3AXD50000038997 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000038997 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000038997 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000038997 — Electrical
ParameterValue
Technical UL/Output Current, Heavy-Duty Use (UL)34.0 A

Product details

Drive ratings and duty selection

The ABB 3AXD50000038997 is an ACH580-01 wall-mounted LV AC drive built for HVAC fan and pump control. Normal-use output is 22 kW at 45 A on 400 V three-phase supply, with a heavy-duty rating of 18.5 kW at 37.7 A for higher-torque loads like compressors or conveyors. Light-overload duty delivers 22.0 kW at 42.8 A, so the 45 A normal-use figure is the one to size branch protection and cabling against. Input accepts 380 to 480 V at 47.5 to 63 Hz — covers 50/60 Hz grids globally. Standby loss is 16 W, and the drive is rated IE2 efficiency class. Sound pressure at 76 dB(A) means it is audible in a mechanical room but not objectionable next to a chiller.

Enclosure, mounting, and environment

IP21 with NEMA Type 1 enclosure suits indoor installation away from washdown or dust. Wall-mounted in frame size R3. Ambient temperature max 40 °C, altitude 1000 m without derating — above that, expect current reduction. Operating humidity up to 95% RH non-condensing. The drive includes a control unit and a lithium coin cell (CR2032, 220 mAh) for real-time clock backup. Two analog inputs and two analog outputs are available for pressure or temperature transducers; six digital inputs and three digital outputs handle start/stop, fault reset, and status feedback.

Frequently asked questions

What compliance documentation does this drive carry?

RoHS compliant per EU Directive 2011/65/EU (date 2024-05-08). REACH declaration confirms substances above 0.1% mass percentage (date 2025-09-05). UL listing covers 30 Hp light-overload at 44.0 A. SCIP number 8e1cd225-4cd2-4db1-8a7b-419a51ce1ae3 Finland is registered for EU waste tracking.

What is the difference between normal-use and heavy-duty ratings on this drive?

Normal-use output is 22 kW at 45 A for variable-torque HVAC loads (fans, centrifugal pumps). Heavy-duty is 18.5 kW at 37.7 A for constant-torque loads like conveyors or positive-displacement pumps. Light-overload sits at 22.0 kW and 42.8 A. The heavy-duty figure is the one to use for sizing when the load profile includes breakaway torque or short overload cycles.

What is the SCIP number and why does it matter?

SCIP 8e1cd225-4cd2-4db1-8a7b-419a51ce1ae3 Finland is the EU waste-reporting identifier for substances of concern in this drive. It is required for compliance with the Waste Framework Directive if the drive is placed on the EU market.

MPN
3AXD50000038997