Ratings and fit for HVAC
The 3AXD50000039000: Normal-use output is 1.5 kW / 4 A; heavy-duty use drops to 1.1 kW / 3.3 A, and light-overload use holds at 1.5 kW / 3.8 A. Under UL listing, light-overload output is 2 Hp at 3.4 A, heavy-duty UL is 3.0 A. The drive accepts 380-480 V input, 47.5-63 Hz, and draws 60 W power consumption with 14 W standby loss. Efficiency is IE2. Ambient temperature max is 40 °C, humidity up to 95%.
Two analog inputs and two analog outputs are available, plus 6 digital inputs and 3 digital outputs. The drive communicates via BACnet; there is no Industrial Ethernet interface. A CR2032 lithium coin cell (220 mAh, 3 V) backs the real-time clock.