Skip to main content
ABB 3AXD50000039003 — AC Drive (VFD) 480V

ABB 3AXD50000039003 ACH580-01 HVAC Drive, 4 kW, 9.4 A, IP55

MPN3AXD50000039003
Active

ABB ACH580-01 wall-mounted HVAC drive, 3-phase 380-480 V, 4 kW normal use, 9.4 A, IP55, NEMA 12, BACnet, IE2.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000039003 — Power & Output
ParameterValue
Output power, normal duty4 kW
Output current, normal duty9.4 A
Output power, heavy duty3.0 kW
Output current, heavy duty7.2 A
Output power, light overload4.0 kW
Output current, light overload8.9 A
Output current, light overload (UL rating)7.6 A
Apparent power output6.5 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)5 Hp
Standby power loss14 W
3AXD50000039003 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000039003 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType12
Degree of protection (IP)IP55
Mounting typeWall-mounted
3AXD50000039003 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000039003 — Electrical
ParameterValue
Technical UL/Output Current, Heavy-Duty Use (UL)4.8 A

Product details

The ABB 3AXD50000039003 is a wall-mounted HVAC drive rated for 4 kW normal use at 9.4 A on a 3-phase 380-480 V supply. It ships with the control unit included and carries an IP55 / NEMA Type12 enclosure. The drive is actively in production.

Normal-use output is 4 kW at 9.4 A; heavy-duty use drops to 3.0 kW at 7.2 A. Light-overload use is rated at 4.0 kW and 8.9 A. Under UL listing, light-overload output is 5 Hp at 7.6 A, and heavy-duty UL output is 4.8 A. Apparent power output is 6.5 kV·A. Standby loss is 14 W, and total power consumption at rated load is 136 W. Efficiency class is IE2.

The drive provides 2 analog inputs and 2 analog outputs, plus 6 digital inputs and 3 digital outputs. Communication is via BACnet; there is no industrial Ethernet interface onboard. The real-time clock is backed by a CR2032 lithium coin cell (220 mAh, 3 V).

Frequently asked questions

What is the SCIP number for this drive?

SCIP: 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland.

Does this drive include a control unit?

Yes, the drive is supplied with control unit included.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU (RoHS date 20240508). REACH declaration confirms substances >0.1% (REACH date 20250905). UL listing covers light-overload at 5 Hp / 7.6 A and heavy-duty at 4.8 A.

MPN
3AXD50000039003