The ABB 3AXD50000039015 is an ACQ580-01 wall-mounted drive rated 0.75 kW normal-use output (Pn) at 2.6 A (In) on a 380–480 V three-phase supply. Heavy-duty use derates to 0.6 kW (PhD) at 1.8 A (IhD).
The 2.6 A normal-use current (In) is the figure to match against your motor nameplate at 400 V. The 0.98 power factor reflects the built-in input rectifier — no external PF correction needed for most installations. IP21 enclosure suits indoor, dry environments. If the installation sees washdown or condensation, you will need a higher IP rating or a separate enclosure. The 40 °C maximum ambient temperature is standard for most control rooms; derate output current if ambient exceeds that.
This drive is built for water and wastewater applications — pumping, aeration, filtration. The ACQ580 series includes application-specific features like pump cleaning and flow control algorithms. The wall-mount format and IP21 allow direct mounting in a dry electrical room near the motor.
Integration notes
Wall-mounted with frame size R1 — plan for the gland plate entry at the bottom and clearance for the CAN communication cable. The drive includes the control unit, so no separate controller module is needed. Analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 3 outputs. Standby loss is 14 W; factor that into panel cooling.