Skip to main content
ABB 3AXD50000039015 — AC Drive (VFD) 480V

ABB 3AXD50000039015 ACQ580-01 Drive, 0.75 kW, 2.6 A

MPN3AXD50000039015
Active

ABB ACQ580-01 wall-mounted drive, 0.75 kW, 2.6 A, 380-480 V, IP21, frame size R1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000039015 — Power & Output
ParameterValue
Output power, normal duty0.75 kW
Output current, normal duty2.6 A
Output power, heavy duty0.6 kW
Output current, heavy duty1.8 A
Output power, light overload0.75 kW
Output current, light overload2.5 A
Apparent power output1.8 kV·A
Efficiency class (IE)IE2
Standby power loss14 W
3AXD50000039015 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000039015 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000039015 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3AXD50000039015 is an ACQ580-01 wall-mounted drive rated 0.75 kW normal-use output (Pn) at 2.6 A (In) on a 380–480 V three-phase supply. Heavy-duty use derates to 0.6 kW (PhD) at 1.8 A (IhD).

The 2.6 A normal-use current (In) is the figure to match against your motor nameplate at 400 V. The 0.98 power factor reflects the built-in input rectifier — no external PF correction needed for most installations. IP21 enclosure suits indoor, dry environments. If the installation sees washdown or condensation, you will need a higher IP rating or a separate enclosure. The 40 °C maximum ambient temperature is standard for most control rooms; derate output current if ambient exceeds that.

This drive is built for water and wastewater applications — pumping, aeration, filtration. The ACQ580 series includes application-specific features like pump cleaning and flow control algorithms. The wall-mount format and IP21 allow direct mounting in a dry electrical room near the motor.

Integration notes

Wall-mounted with frame size R1 — plan for the gland plate entry at the bottom and clearance for the CAN communication cable. The drive includes the control unit, so no separate controller module is needed. Analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 3 outputs. Standby loss is 14 W; factor that into panel cooling.

Frequently asked questions

What is the SCIP number for this drive?

The SCIP number is a5c3dd71-8ecd-44d9-98e4-45c53b6836e1, registered in Finland.

What compliance documentation is available?

RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863, with RoHS date 20240508. REACH declaration confirms substances above 0.1 mass percentage, with date 20250905.

MPN
3AXD50000039015