IP21 with NEMA Type 1 enclosure suits indoor installations where dripping water and limited dust are the concern — not washdown or outdoor exposure. Communication is CAN-based; no onboard Industrial Ethernet. The 6 digital inputs and 3 digital outputs, plus 2 analog inputs and 2 analog outputs, give enough I/O for a standalone pump or fan controller without an expansion module.
Overload duty and efficiency
Three duty ratings let you match the drive to the load profile. Light-overload (PlD 3 kW, IlD 6.8 A) covers variable-torque fans and pumps. Normal use (Pn 3 kW, In 7.2 A) is the standard selection for constant-torque applications. Heavy-duty (PhD 2.2 kW, IhD 5.6 A) provides headroom for high-starting-torque loads like conveyors or crushers. Efficiency is rated IE2, which is the baseline for this power class. Standby loss is 14 W; full-load power consumption is 98 W. Power factor at rated load is 0.98.
Altitude rating is 4000 m, which covers most installations above sea level without derating. Operating temperature max is 40 °C; humidity range 5 to 95% non-condensing. Sound level is 59 dB(A).