The ABB 3AXD50000039028 is the order code for an ACQ580-01-026A-4 low-voltage AC wall-mounted drive, sized for 11 kW normal-duty output at 25.0 A from a 380–480 V three-phase supply. The drive includes a control unit, mounts on the wall in frame size R2, and draws 383 W at rated load with a standby loss of 15 W.
Normal-duty output is 11 kW / 25.0 A; heavy-duty use drops to 7.5 kW / 17.0 A, and light-overload use stays at 11 kW / 23.8 A. The heavy-duty figure governs continuous operation at higher ambient or with a demanding load profile. Altitude rating is 4000 m. Efficiency is rated IE2, with a power factor of 0.98. Sound level is 64 dB(A), typical for a drive of this power class.
The drive carries 2 analog inputs, 2 analog outputs, 6 digital inputs, and 3 digital outputs — enough for basic pump/fan control without an expansion module. Communication is via CAN; there are no onboard industrial Ethernet interfaces (0 hardware interfaces for Ethernet). If Ethernet connectivity is required, an optional fieldbus adapter must be added.