Enclosure and environment — rated for wet plant floors
The 3AXD50000039032: IP55 and NEMA Type 12 enclosure means this drive handles hose-down, dust, and condensation common in water treatment and wastewater plants. Maximum ambient 40 °C, altitude up to 4000 m without derating. Operating humidity 5–95% non-condensing. Wall-mount it directly — no extra cabinet required for the drive itself.
Efficiency and standby — what it draws when idle matters
Rated IE2 efficiency level. Standby loss is 14 W — relevant for sites where the drive sits idle between pump cycles. Power factor 0.98 at rated load keeps the line side clean. Sound level 59 dB(A) — quiet enough for a pump house but not silent.
Control and I/O — CAN-based, with analog and digital channels
Communication is CAN protocol — no onboard Ethernet (0 hardware interfaces for Industrial Ethernet). Two analog inputs and two analog outputs for process signals (pressure, flow, level). Six digital inputs and three digital outputs handle start/stop, fault reset, and status feedback. The included control unit carries a CR2032 lithium coin cell (220 mAh) for real-time-clock backup.