Skip to main content
ABB 3AXD50000039037 — AC Drive (VFD) 480V

ABB 3AXD50000039037 ACQ580-01 Drive, 4 kW, 9.4 A, IP55

MPN3AXD50000039037
Active

ABB ACQ580-01 series, LV AC wall-mounted drive, 3AXD50000039037, 4 kW normal-use output, 9.4 A, 380-480 V, IP55, frame R1.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000039037 — Power & Output
ParameterValue
Output power, normal duty4 kW
Output current, normal duty9.4 A
Output power, heavy duty3 kW
Output current, heavy duty7.2 A
Output power, light overload4 kW
Output current, light overload8.9 A
Apparent power output6.5 kV·A
Efficiency class (IE)IE2
Standby power loss14 W
3AXD50000039037 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000039037 — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType12
Degree of protection (IP)IP55
Mounting typeWall-mounted
3AXD50000039037 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

It delivers 4 kW normal-use output at 9.4 A from a 380-480 V three-phase supply, with a heavy-duty rating of 3 kW at 7.2 A for tougher load profiles.

Three duty classes are defined: normal use (Pn 4 kW, In 9.4 A), light-overload (PlD 4 kW, IlD 8.9 A), and heavy-duty (PhD 3 kW, IhD 7.2 A). The heavy-duty figure governs continuous operation on a pump or fan with a constant-torque component — if your motor nameplate exceeds 7.2 A at the shaft, step up a frame. The normal-use rating matches a standard variable-torque centrifugal load.

Enclosure, mounting, and environment

IP55 with NEMA Type 12 enclosure, wall-mounted, frame size R1. Rated for ambient temperatures up to 40 °C and altitudes to 4000 m — no derating needed at moderate elevation. Operating humidity range 5 to 95 % non-condensing. Standby loss is 14 W; sound level 59 dB(A). The SCIP number is 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland.

Two analog inputs and two analog outputs are onboard. Digital I/O counts 6 inputs and 3 outputs. Communication is via CAN; no onboard Industrial Ethernet interface. The control unit is included. Power consumption is 136 W, with an apparent power output of 6.5 kV·A. Power factor is 0.98. Efficiency class IE2.

Frequently asked questions

What are the output ratings for normal and heavy-duty use?

Normal use: 4 kW, 9.4 A. Heavy-duty use: 3 kW, 7.2 A. Light-overload use: 4 kW, 8.9 A.

What enclosure protection does this drive have?

IP55 with NEMA Type 12, wall-mounted, frame R1.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863. REACH declaration confirms substances above 0.1 mass percentage.

What is the SCIP number for this drive?

SCIP: 85773b93-5c45-45c8-a538-ebdaaaf96ece Finland.

MPN
3AXD50000039037