Skip to main content
ABB 3AXD50000041423 — AC Drive (VFD) 480V

ABB 3AXD50000041423 ACS580-07 Cabinet Drive, 110 kW, 206 A

MPN3AXD50000041423
Active

ABB ACS580-07, LV AC general purpose cabinet-built drive, 110 kW, 206 A, 400 V, IP21, frame R7.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000041423 — Power & Output
ParameterValue
Output power, normal duty110 kW
Output current, normal duty206 A
Output power, heavy duty90 kW
Output current, heavy duty169 A
Output power, light overload110 kW
Output current, light overload196 A
Output current, light overload (UL rating)180 A
Apparent power output143 kV·A
Output power, light overload (UL rating, Hp)150 Hp
3AXD50000041423 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000041423 — Mechanical & Cooling
ParameterValue
Frame sizeR7
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeCabinet-built
3AXD50000041423 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000041423 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)125 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)156 A

Product details

Duty ratings that match the load profile

The 3AXD50000041423: Normal-use (Pn 110 kW, In 206 A) covers constant-torque applications like conveyors and pumps. Heavy-duty use (PhD 90 kW, IhD 169 A) handles higher overloads — crushers, extruders, mixers. Light-overload use (PlD 110 kW, IlD 196 A) suits variable-torque loads such as fans and centrifugal pumps. The UL listing mirrors these: heavy-duty 125 Hp / 156 A, light-overload 150 Hp / 180 A.

I/O, communication, and environmental limits

The drive provides 2 analog inputs, 2 analog outputs, and 6 digital inputs / 3 digital outputs. Communication is via CAN. Operating frequency range is 47.5–63 Hz. Ambient temperature maximum is 40 °C; operating humidity 5 to 95%. Sound pressure level is 67 dB(A). A lithium coin cell (CR2032, 220 mAh, 3 V) backs the real-time clock.

Frequently asked questions

What are the key duty ratings for this drive?

Normal use: 110 kW / 206 A. Heavy-duty use: 90 kW / 169 A. Light-overload use: 110 kW / 196 A.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1% (date 20250905). SCIP number f8697513-3243-4f24-9777-7dbe1d791662 Finland.

What is the enclosure rating and mounting type?

IP21 / NEMA Type 1, cabinet-built — designed for indoor installation in a control cabinet.

MPN