Skip to main content
ABB 3AXD50000041426 — AC Drive (VFD) 480V

ABB 3AXD50000041426 ACS580-07 Cabinet Drive, 200 kW, 363 A

MPN3AXD50000041426
Active

ABB ACS580-07 cabinet-built drive, 3AXD50000041426, 200 kW / 363 A normal duty, 380-480 V, IP21, NEMA 1, frame R9.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000041426 — Power & Output
ParameterValue
Output power, normal duty200 kW
Output current, normal duty363 A
Output power, heavy duty160 kW
Output current, heavy duty293 A
Output power, light overload200 kW
Output current, light overload345 A
Output current, light overload (UL rating)361 A
Apparent power output251 kV·A
Output power, light overload (UL rating, Hp)300 Hp
3AXD50000041426 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000041426 — Mechanical & Cooling
ParameterValue
Frame sizeR9
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeCabinet-built
3AXD50000041426 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000041426 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)250 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)302 A

Product details

The ABB 3AXD50000041426 is a general-purpose cabinet-built drive rated for 200 kW normal use at 363 A output on a 380–480 V three-phase supply. It ships as a complete cabinet with the control unit included, frame size R9, IP21 with NEMA Type 1 enclosure. The heavy-duty rating is 160 kW / 293 A, and the light-overload rating is 200 kW / 345 A. UL ratings are 250 Hp / 302 A heavy-duty and 300 Hp / 361 A light-overload.

For higher-torque starts or shock loads, the heavy-duty curve drops to 293 A; that's the number to use when sizing for a crusher or extruder. The apparent power output of 251 kVA gives the transformer or generator sizing figure. Ambient must stay at or below 40 °C; above that, derate per the standard curve. The drive draws 5868 W at rated load, so factor that into panel cooling. The 2 analog inputs and 2 analog outputs handle speed reference and feedback signals. The 6 digital inputs and 3 digital outputs cover start/stop, fault reset, and status. Communication is CAN-based; there is no onboard industrial Ethernet port, so if you need Profinet or EtherNet/IP, plan for an external gateway or option module.

Cabinet-built means it arrives as a self-contained enclosure — no separate panel build needed. Mounting is floor-standing; the R9 frame is sized for a 200 kW drive. The IP21 / NEMA 1 rating allows indoor installation in clean, dry environments. Operating humidity range is 5 to 95% non-condensing. The sound level is 68 dB(A) — noticeable but not deafening; ear protection is recommended for prolonged proximity.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declaration confirms substances above 0.1% mass percentage (date 20250905). UL ratings are provided for heavy-duty and light-overload use.

What is the SCIP number for this drive?

The SCIP number is 105dd15e-a9d4-40aa-a399-53b46cd95cf3 Finland.

What does the drive include?

The drive includes a control unit as part of the cabinet-built assembly.

MPN
3AXD50000041426