ABB 3AXD50000043439 — AC Drive (VFD) 480V

3AXD50000043439 ABB ACS880-04F-880A-3 Drive Module, 500 kW,

MPN3AXD50000043439
Active

ABB ACS880-04F-880A-3 LV AC industrial flange-mounted single drive module, IEC: Pn 500 kW, 880 A, 400 V, IP20, frame size R11.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000043439 — Power & Output
ParameterValue
Output power, normal duty500 kW
Output current, normal duty880 A
Output power, heavy duty400 kW
Output current, heavy duty725 A
Output power, light overload500 kW
Output current, light overload865 A
Apparent power output610 kV·A
Efficiency class (IE)IE2
Standby power loss423 W
3AXD50000043439 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000043439 — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000043439 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

The ABB 3AXD50000043439 is an ACS880-04F-880A-3 LV AC industrial flange-mounted single drive module, rated for 500 kW normal-duty output power and 880 A continuous output current on a 400 V three-phase supply. Heavy-duty use drops to 400 kW and 725 A; light-overload use holds at 500 kW and 865 A. Input voltage range is 380–415 V, 47.5–63 Hz, three-phase. Standby losses sit at 423 W; full-load power consumption hits 10863 W. The apparent power output is 610 kV·A, which gives headroom for motor inrush and short-term overloads without tripping the line-side breaker.

Integration notes

Frame size R11, flange-mounted — plan for the physical footprint and gland-plate entry before the panel layout is locked. The module includes the control unit, so no separate controller purchase is needed. Communication is CAN-based; no onboard Ethernet, so if you need PROFINET or EtherNet/IP, budget for an optional communication adapter module. Analog I/O: 2 inputs, 2 outputs. Digital I/O: 6 inputs, 2 outputs. Sound pressure level is 75 dB(A) — not silent; ear protection is warranted if the drive is in a manned room. Operating humidity range is 5–95% RH, non-condensing. Altitude rating is 4000 m, so it handles high-altitude installations without derating up to that ceiling. The battery is a CR2032 lithium coin cell, 220 mAh, 3 V, two pieces, 6 g total — typical for parameter backup. Expect to replace it every few years if the drive is powered off for extended periods.

Frequently asked questions

What compliance documentation does this drive module carry?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863, dated 2024-05-08. REACH declaration confirms substances above 0.1% mass percentage, dated 2025-03-20. The spec does not list UL or IEC certification explicitly, but the module is designed to IEC standards per the description.

What is the altitude rating for this module?

It is rated for operation up to 4000 m without derating.

Does the module include a control unit?

Yes, the Includes field lists 'Control unit', so no separate controller purchase is required.

What are the key output ratings for normal and heavy-duty use?

Normal-duty: 500 kW, 880 A. Heavy-duty: 400 kW, 725 A. Light-overload: 500 kW, 865 A. All at 400 V three-phase.