Skip to main content
ABB 3AXD50000046000 — AC Drive (VFD) 480V

ABB 3AXD50000046000 ACS880-04F Drive Module, 250 kW, 504 A

MPN3AXD50000046000
Active

ABB ACS880-04F LV AC industrial flange-mounted single drive module, IEC: Pn 250 kW, 504 A, 400 V, frame size R11, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3AXD50000046000 — Power & Output
ParameterValue
Output power, normal duty250 kW
Output current, normal duty504 A
Output power, heavy duty200 kW
Output current, heavy duty361 A
Output power, light overload250 kW
Output current, light overload485 A
Apparent power output349 kV·A
Efficiency class (IE)IE2
Standby power loss423 W
3AXD50000046000 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000046000 — Mechanical & Cooling
ParameterValue
Frame sizeR11
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000046000 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C

Product details

Drive selection memo: ACS880-04F, 250 kW, frame R11

The ABB 3AXD50000046000 is an LV AC flange-mounted single drive module rated for 250 kW normal-use output at 504 A on a 400 V three-phase supply (380…415 V, 47.5…63 Hz). Frame size R11, IP20, NEMA Open Type — built for panel integration, not standalone floor mounting. Heavy-duty use drops to 200 kW / 361 A; light-overload use holds at 250 kW / 485 A. Standby loss sits at 423 W, full-load power consumption at 4625 W. Ambient max is 40 °C, altitude rated to 4000 m — derate above that, but the 4000 m ceiling covers most high-altitude installations without a special build.

What's in the box and what connects

The module ships with the control unit included — no separate order for the brains. It carries 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs, plus a CAN interface. No onboard industrial Ethernet (0 hardware interfaces for that), so if you need PROFINET or EtherNet/IP, plan for an optional fieldbus adapter module. A lithium coin cell (CR2032, 220 mAh, 3 V, two pieces) backs up the real-time clock and parameter storage. At 75 dB(A) sound level, it's audible in a quiet control room — ear protection not required, but you'll know it's running.

Frequently asked questions

What are the key ratings for this drive module?

Normal-use output is 250 kW at 504 A; heavy-duty is 200 kW at 361 A; light-overload is 250 kW at 485 A. Input is 380…415 V three-phase, 47.5…63 Hz. Frame size R11, IP20, NEMA Open Type.

What compliance documentation is available?

RoHS compliant per EU Directive 2011/65/EU and Amendment 2015/863 (RoHS date 20240508). REACH declaration confirms substances >0.1 mass percentage (REACH date 20250320). WEEE category 4 applies.

Does the module include a control unit?

Yes, the control unit is included with the drive module — no separate purchase needed.

What is the altitude rating?

Rated for installation up to 4000 m without derating.

MPN
3AXD50000046000