Skip to main content
ABB 3AXD50000047393 — AC Drive (VFD) 480V

ABB 3AXD50000047393 ACS880-11 Regenerative Drive, 55 kW, 105

MPN3AXD50000047393
Active

ABB, ACS880-11 series, LV AC industrial wall-mounted regenerative single drive, IEC: Pn 55 kW, 105 A, 400 V, 3AXD50000047393.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000047393 — Power & Output
ParameterValue
Output power, normal duty55 kW
Output current, normal duty105 A
Output power, heavy duty45 kW
Output current, heavy duty87 A
Output power, light overload55 kW
Output current, light overload100 A
Apparent power output73 kV·A
Efficiency class (IE)IE2
Standby power loss75 W
3AXD50000047393 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000047393 — Mechanical & Cooling
ParameterValue
Frame sizeR8
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000047393 — Environmental
ParameterValue
Temperature rating (max.)Maximum +55 °C

Product details

The 3AXD50000047393: Heavy-duty use drops to 45 kW / 87 A, and light-overload use holds at 55 kW / 100 A. Apparent power output is 73 kV·A. The drive comes with a control unit included, frame size R8, and standby loss of 75 W.

Wall-mounted, IP21 enclosure (NEMA Type 1). Rated for ambient temperatures up to +55 °C, operating humidity 5–95% RH, and altitude up to 4000 m. Sound level is 68 dB(A). Power consumption at rated load is 1593 W.

I/O and communications

Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is via CAN bus; there are no industrial Ethernet interfaces on this variant. A lithium coin cell (CR2032, 220 mAh, 3 V, two pieces) backs up the real-time clock.

Frequently asked questions

What are the key output ratings for this drive?

Normal-duty (light overload) output is 55 kW at 105 A. Heavy-duty output is 45 kW at 87 A. Apparent power output is 73 kV·A.

What is the enclosure type and mounting?

Wall-mounted, IP21 (NEMA Type 1). Suitable for indoor use where dripping water and limited dust ingress are acceptable.

What communication protocols does it support?

CAN bus is the listed communication protocol. There are no onboard industrial Ethernet interfaces on this variant.

MPN