Skip to main content
ABB 3AXD50000047497 — AC Drive (VFD) 480V

ABB 3AXD50000047497 ACS880-11 Regenerative Drive, 30 kW

MPN3AXD50000047497
Active

ABB ACS880-11 regenerative single drive, 30 kW normal-use output, 61 A, 400 V, IP21, wall-mounted, frame R6.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000047497 — Power & Output
ParameterValue
Output power, normal duty30 kW
Output current, normal duty61 A
Output power, heavy duty22 kW
Output current, heavy duty45 A
Output power, light overload30 kW
Output current, light overload58 A
Apparent power output42 kV·A
Efficiency class (IE)IE2
Standby power loss51 W
3AXD50000047497 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000047497 — Mechanical & Cooling
ParameterValue
Frame sizeR6
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000047497 — Environmental
ParameterValue
Temperature rating (max.)Maximum +55 °C

Product details

It delivers 22 kW heavy-duty and 30 kW light-overload, with corresponding currents of 45 A and 58 A. The drive accepts 380–415 V input at 47.5–63 Hz and is enclosed to IP21 with a NEMA Type1 rating.

Normal-use rating is 30 kW / 61 A. Heavy-duty rating is 22 kW / 45 A for higher overload cycles.

Wall-mounted in frame size R6, the drive is rated for operation up to +55 °C ambient and altitudes to 4000 m without derating. The IP21 enclosure suits indoor, clean environments — no washdown or dust exposure. Standby loss is 51 W; sound level is 71 dB(A). The drive includes a control unit and uses a CR2032 lithium coin cell for backup (2 pcs, 220 mAh, 3 V).

Onboard I/O includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is via CAN; there is no onboard Industrial Ethernet. For fieldbus integration, an optional adapter module would be needed — the base drive does not include a slot for Ethernet modules.

Frequently asked questions

What are the key output ratings for this drive?

Normal-use output is 30 kW at 61 A; heavy-duty is 22 kW at 45 A; light-overload is 30 kW at 58 A. Input is 380–415 V three-phase, 47.5–63 Hz.

What is the SCIP number for this drive?

The SCIP number is 2e5fdce1-7092-448c-9584-f0fd2b6a9f47 (Finland).

What compliance documentation is available?

RoHS compliance per EU Directive 2011/65/EU and Amendment 2015/863 (date 20240508). REACH compliance confirmed (date 20250905). The drive is exempt from EU ecodesign energy efficiency requirements.

What is the maximum operating altitude?

The drive is rated for operation up to 4000 m altitude.

MPN
3AXD50000047497