Specifications

3AXD50000047498 — Power & Output
ParameterValue
Output power, normal duty37 kW
Output current, normal duty72 A
Output power, heavy duty30 kW
Output current, heavy duty61 A
Output power, light overload37 kW
Output current, light overload68 A
Apparent power output50 kV·A
Efficiency class (IE)IE2
Standby power loss51 W
3AXD50000047498 — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000047498 — Mechanical & Cooling
ParameterValue
Frame sizeR6
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted
3AXD50000047498 — Environmental
ParameterValue
Temperature rating (max.)Maximum +55 °C

Product details

The ABB 3AXD50000047498 is an LV AC industrial wall-mounted regenerative single drive, rated for 37 kW normal use and 72 A output current on a 380–415 V three-phase supply. It carries a heavy-duty rating of 30 kW / 61 A and a light-overload rating of 37 kW / 68 A.

Normal-use output (Pn 37 kW, In 72 A) is the rating for typical variable-torque loads like pumps and fans. Heavy-duty use (PhD 30 kW, IhD 61 A) covers constant-torque applications such as conveyors or extruders. Light-overload use (PlD 37 kW, IlD 68 A) sits between the two. Rated for 380–415 V three-phase input, 47.5–63 Hz. The IP21 / NEMA Type 1 enclosure suits indoor, non-hosedown environments. Frame size R6 is wall-mounted, so plan for the gland plate area and clearance for the heatsink airflow. Standby loss is 51 W — not negligible if the drive stays powered but idle for long periods. Efficiency is IE2; note the ecodesign exemption for regenerative drives (EU/2019/1781 §2.3.c) means no energy-efficiency data is required for this class.

The control unit includes 2 analog inputs, 2 analog outputs, 6 digital inputs, and 2 digital outputs. Communication is CAN-based; there are no onboard Industrial Ethernet ports, so a separate fieldbus adapter is needed for PROFINET or EtherNet/IP integration. The drive contains two CR2032 lithium coin cells (220 mAh, 3 V each) for backup — factor these into the preventive maintenance schedule; they are not user-serviceable without opening the unit.

Operates at ambient temperatures up to +55 °C, with 5–95% non-condensing humidity. Altitude rating is 4000 m. Sound level is 71 dB(A).

Frequently asked questions

What are the key output ratings for this drive?

Normal use: 37 kW / 72 A. Heavy-duty use: 30 kW / 61 A. Light-overload use: 37 kW / 68 A. Input voltage is 380–415 V three-phase.

What compliance documentation is available for 3AXD50000047498?

RoHS compliant per EU 2011/65/EU and Amendment 2015/863 (date 20240508). REACH declared (date 20250905). SCIP number 2e5fdce1-7092-448c-9584-f0fd2b6a9f47. No UL or IEC certification numbers are listed in this record.

What is the SCIP number for this drive?

SCIP: 2e5fdce1-7092-448c-9584-f0fd2b6a9f47, registered in Finland.