Skip to main content
ABB 3AXD50000047643 — AC Drive (VFD) 480V

ABB 3AXD50000047643 ACS560-01-05A6-4, 2.2 kW, 5.6 A

MPN3AXD50000047643
Active

ABB ACS560-01-05A6-4, 3AXD50000047643, 2.2 kW normal-use output, 5.6 A, 380-480 V 3-phase input, IP20, wall-mount, frame size R0.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Power & Output

3AXD50000047643 — Power & Output
ParameterValue
Output power, normal duty2.2 kW
Output current, normal duty5.6 A
Output power, heavy duty1.5 kW
Output current, heavy duty4 A
Output power, light overload2.2 kW
Output current, light overload5.3 A
Apparent power output4.0 kV·A
Efficiency class (IE)IE2
Standby power loss15 W

Input / Supply

3AXD50000047643 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47 ... 63 Hz

Mechanical & Cooling

3AXD50000047643 — Mechanical & Cooling
ParameterValue
Frame sizeR0
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeWall-mounted

Environmental

3AXD50000047643 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C

Product details

The ABB 3AXD50000047643 is an ACS560-01-05A6-4 general-purpose drive rated for 2.2 kW normal-use output (5.6 A) on a 380-480 V three-phase supply. Heavy-duty rating is 1.5 kW / 4 A; light-overload matches the normal-use figure at 2.2 kW / 5.3 A. Efficiency is IE2, which is the baseline for this power class in most regions — no premium-efficiency premium, but compliant for standard industrial installations. Standby loss of 15 W matters if the drive stays powered during idle periods; it's low enough that a 24 V control supply fan can handle the heat in a sealed cabinet.

Frame size R0 is the smallest in the ACS560 family — wall-mount only, no flange kit needed. IP20 means it's for clean, dry indoor panels; no washdown or dust tolerance. Maximum ambient 50 °C, so keep it out of hot spots near braking resistors or other drives. Open-type enclosure (NEMA 1 equivalent) means it expects overcurrent protection upstream per the local code. WEEE category 5 (small equipment) means end-of-life recycling obligations apply in EU markets — factor that into your compliance paperwork if you're shipping into Europe.

Frequently asked questions

What is the frame size and how does it mount?

Frame size R0, wall-mounted. It's the smallest ACS560 frame — no flange, no through-panel kit. IP20, so indoor panel use only.

What are the key output ratings for motor sizing?

Normal-use (variable torque): 2.2 kW / 5.6 A. Heavy-duty (constant torque): 1.5 kW / 4 A. Light-overload matches normal-use at 2.2 kW / 5.3 A. Input is 380-480 V three-phase.

What is the standby power loss?

15 W. Low enough for passive cooling in most panels, but check your enclosure's thermal budget if you're stacking multiple drives.

MPN
3AXD50000047643