Power & Output

3AXD50000047648 — Power & Output
ParameterValue
Output power, normal duty11 kW
Output current, normal duty25 A
Output power, heavy duty7.5 kW
Output current, heavy duty17 A
Output power, light overload11.0 kW
Output current, light overload23.8 A
Apparent power output17 kV·A
Efficiency class (IE)IE2
Standby power loss26 W

Input / Supply

3AXD50000047648 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47 ... 63 Hz

Mechanical & Cooling

3AXD50000047648 — Mechanical & Cooling
ParameterValue
Frame sizeR2
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeWall-mounted

Environmental

3AXD50000047648 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C

Product details

The ABB ACS560-01-025A-4 (3AXD50000047648) is an 11 kW variable-frequency drive in frame size R2, rated 25 A for normal-duty motor loads on a 380–480 V three-phase supply. Heavy-duty use drops to 7.5 kW / 17 A, and light-overload use is 11.0 kW / 23.8 A — so the normal-use figure is the one to match against your motor nameplate for continuous duty, while the heavy-duty rating governs applications with higher starting or cyclic overloads.

Standby loss of 26 W is the heat the drive dissipates when the motor is not running — relevant for panel thermal calculations and for installations where the drive stays powered continuously but the load cycles. Wall-mounting is the listed method, which matches the frame R2 footprint for a compact panel layout.

Frequently asked questions

What is the frame size of this drive?

The frame size is R2, which defines the physical envelope and mounting pattern for panel integration.

What is the standby loss of this drive?

Standby loss is 26 W — the power the drive consumes when the motor is not running, relevant for thermal management in the enclosure.

What are the key output ratings for normal and heavy-duty use?

Normal-use output is 11 kW / 25 A; heavy-duty use is 7.5 kW / 17 A; light-overload use is 11.0 kW / 23.8 A. The normal rating matches continuous motor load, while the heavy-duty rating covers higher overload profiles.