ABB 3AXD50000047793 — AC Drive (VFD) 480V

ABB 3AXD50000047793 ACS480 Drive Module, 11 kW, 25 A

MPN3AXD50000047793
Active

ABB ACS480 series, LV AC general purpose drive module, 3AXD50000047793, 11 kW / 25 A normal use, 380-480 V 3-phase, IP20, R3 frame.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000047793 — Power & Output
ParameterValue
Output power, normal duty11 kW
Output current, normal duty25 A
Output power, heavy duty7.5 kW
Output current, heavy duty17.0 A
Output power, light overload11.0 kW
Output current, light overload23.8 A
Output current, light overload (UL rating)21.0 A
Apparent power output17 kV·A
Efficiency class (IE)IE2
Standby power loss26 W
3AXD50000047793 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000047793 — Mechanical & Cooling
ParameterValue
Frame sizeR3
NEMA enclosure typeOpen Type
Degree of protection (IP)IP20
Mounting typeModule
3AXD50000047793 — Environmental
ParameterValue
Temperature rating (max.)Maximum 50 °C
3AXD50000047793 — Electrical
ParameterValue
Technical UL/Output Current, Heavy-Duty Use (UL)14.0 A

Product details

The ABB 3AXD50000047793 is an ACS480-04-026A-4 LV AC general purpose drive module rated for 11 kW normal-use output at 25 A on a 380-480 V three-phase supply. It includes the control unit, so this order code covers the complete drive — not a bare power stage.

Normal-use output is 11 kW at 25 A; heavy-duty use drops to 7.5 kW at 17.0 A. Light-overload use is rated at 11.0 kW and 23.8 A. Under UL listing the normal-use current is 21 A, heavy-duty 14.0 A, light-overload 21.0 A. If your application runs a constant-torque load near the motor nameplate, size against the heavy-duty figure — that 17.0 A (IEC) or 14.0 A (UL) is the continuous rating for a 7.5 kW motor on a conveyor or positive-displacement pump. Apparent power output is 17 kV·A, power consumption at rated load is 390 W, and standby loss sits at 26 W. That standby figure matters if the drive stays powered but idle for long periods — 26 W is low enough to skip a contactor on the line side in most panels.

Two analog inputs and two analog outputs are on board, plus 6 digital inputs and 3 digital outputs. Communication is via CAN; there is no industrial Ethernet interface on this variant. If you need Ethernet/IP, PROFINET, or Modbus TCP, you will need the fieldbus adapter module that plugs into the option slot.

Physical and environmental

R3 frame size, IP20 enclosure, open type per NEMA. Maximum ambient temperature is 50 °C. Frequency range is 47.5 to 63 Hz. Sound level is 65.8 dB(A) — noticeable in a quiet room but unremarkable on a factory floor.

The control board includes a CR2032 lithium coin cell (220 mAh, 3 V) that backs up real-time clock and parameter storage.

Frequently asked questions

What compliance documentation is available for this drive?

RoHS compliance follows EU Directive 2011/65/EU and Amendment 2015/863 (date 20230315). REACH declaration confirms substances above 0.1 mass percentage (date 20250905). SCIP number is d47e4459-83a3-4590-a72e-d9674f7109ad Finland. UL current ratings are provided for normal, heavy-duty, and light-overload use.

What does the 'Includes Control unit' mean for this order code?

It means the 3AXD50000047793 ships as a complete drive with the control unit included — not a bare power stage that requires a separate control module.

What are the key ratings for this drive?

Normal-use output is 11 kW at 25 A (IEC) / 21 A (UL). Heavy-duty output is 7.5 kW at 17.0 A (IEC) / 14.0 A (UL). Input is 380-480 V three-phase, 47.5-63 Hz. Frame size R3, IP20.

MPN