Skip to main content
ABB 3AXD50000049030 — AC Drive (VFD) 480V

3AXD50000049030 ABB Drive Control Unit, 355 kW, 650 A, R10

MPN3AXD50000049030
Active

ABB 3AXD50000049030, ACS880-series control unit, R10 frame, 355 kW / 650 A normal-use output, IP00, 380–480 VAC input.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3AXD50000049030 — Power & Output
ParameterValue
Output power, normal duty355 kW
Output current, normal duty650 A
Output power, heavy duty250 kW
Output current, heavy duty477 A
Output power, light overload355 kW
Output current, light overload634 A
Output current, light overload (UL rating)623 A
Apparent power output450 kV·A
Efficiency class (IE)IE2
Output power, light overload (UL rating, Hp)500 Hp
Standby power loss423 W
3AXD50000049030 — Input / Supply
ParameterValue
Input voltage range380 ... 480 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3AXD50000049030 — Mechanical & Cooling
ParameterValue
Frame sizeR10
NEMA enclosure typeOpen Type
Degree of protection (IP)IP00
Mounting typeModule
3AXD50000049030 — Environmental
ParameterValue
Temperature rating (max.)Maximum 40 °C
3AXD50000049030 — Electrical
ParameterValue
Technical UL/Output Power, Heavy-Duty Use (UL)400 Hp
Technical UL/Output Current, Heavy-Duty Use (UL)477 A

Product details

The ABB 3AXD50000049030 is a control unit for the ACS880 drive family, frame size R10. It delivers 355 kW normal-use output at 650 A (light-overload 634 A, heavy-duty 477 A at 250 kW) from a 380–480 V three-phase supply, 47.5–63 Hz. The unit is IP00, open-type NEMA, and rated for a maximum 40 °C ambient at 1000 m altitude.

Key Ratings in Context

The normal-use output current (650 A) is the figure to size for continuous motor loads; the heavy-duty curve (477 A) governs applications with high starting torque or cyclic overloads. Apparent power rating is 450 kV·A at 0.98 power factor. Standby loss of 423 W and power consumption of 8046 W at rated load define the thermal budget for enclosure sizing. Sound level is 72 dB(A).

Frequently asked questions

What are the key output ratings for this control unit?

Normal-use: 355 kW / 650 A; light-overload: 355 kW / 634 A; heavy-duty: 250 kW / 477 A. UL normal-use: 500 Hp / 650 A; UL heavy-duty: 400 Hp / 477 A.

What is the input voltage and frequency range?

380–480 V three-phase, 47.5–63 Hz.

MPN
3AXD50000049030